Showing posts with label feed water. Show all posts
Showing posts with label feed water. Show all posts

A Better Alternative to Magmeter for Unpolished Condensate Flow Measurement

Veris Accelabar
Veris Accelabar 
A large University was using magnetic flowmeters (Magmeters) to measure the flow of boiler feed water downstream of a condensate polisher. There were occasional system upsets that required the condensate polisher to be bypassed. When this happened, large amounts of debris would be released downstream and pass directly through the Magmeter, causing a build-up of foreign material on the internal sensing surfaces.

A magnetic flowmeter uses an electric current applied to a coil which produces a magnetic field. When conductive liquid flows through the magnetic field, a small voltage, proportional to the liquid velocity, is induced. As long as the interior surfaces of the Magmeter are clean and unobstructed, the meter accurately measures flow. If they get dirty or coated, all bets are off.

It was in the above mentioned upset situations where the University maintenance people were having problems. When upsets occurred, and the condensate polisher had to be by-passed, it meant the Magmeter would also have to be serviced because accuracy could no longer be guaranteed. Servicing the Magmeter was slow and costly. It meant shutting down the line, draining the pipe, removing the flowmeter, cleaning, and then putting it all back together.

Armstrong International’s Veris Group was called in for a consult. After review,  the Veris Group recommended installing an Accelabar® flow meter to offer an alternative solution that could provide reliable flow measurement regardless of an upset condition like unpolished condensate. The Accelabar provided a flow range of 22.5:1 turndown in flow, in a limited straight run scenario. In the past, two transmitters were required to provide the best accuracy across the entire range of the Accelabar. Veris was able to use the Foxboro IDP 10S with its FoxCal™ technology in order to have a combined percent of rate accuracy solution.

The new transmitter installation has 11 separate calibrations loaded into the device. As the differential pressure from the primary element is measured, the transmitter chooses the correct calibration curve. Veris’ solution delivered performance that was previously unattainable with a single differential pressure transmitter.

The Accelabar and Foxboro combined to be best solution, and the Accelabar flow meter is now the University's standard for the boiler feed water measurements.

For more information, contact:

Mead O'Brien, Inc.
10800 Midwest Industrial Blvd
St Louis,  MO 63132
314-423-5161
314-423-5707
www.meadobrien.com